QSSUNHow Many Batteries Does a House Need?
It depends on loads and runtime. The working formula: required energy (kWh) = total load in kW x hours of operation, divided by the battery's allowed depth of discharge.
Products in stock
In depth
Example: a home running a 1.5kW AC, a 0.2kW fridge and 0.2kW of lighting for six night hours needs about 11.4kWh. With lithium at 90% DoD that is roughly 12.7kWh nameplate, so a 15kWh bank in practice.
The same calculation with gel roughly doubles the number because allowed discharge is 50%, i.e. around 23kWh nameplate.
Then translate energy into units: a 15kWh bank can be one 51.2V 300Ah lithium module, or several 12V 200Ah gel batteries in series and parallel.
Related products with specs and prices
| Product | Specifications | Price (SAR) |
|---|---|---|
| QSSUN AGM BATTERY 12V 7AH - UPS بطارية كيوصن 7 امبير | 12V | 45 |
| QSSUN AGM BATTERY 12V 9AH - UPS بطارية كيوصن 9 امبير | 12V | 58 |
| AGM BATTERY 12V 12AH - UPS بطارية كيوصن 12 امبير | 12V | 81 |
| QSSUN AGM BATTERY 12V 18AH - UPS بطارية كيوصن 18 امبير | 12V | 92 |
| QSSUN AGM BATTERY 12V 20AH - UPS بطارية كيوصن 20 امبير | 12V / 20Ah | 150 |
| بطاريه SCB جل 12 فولت 26 امبير فيتنامي | 12V / 26Ah | 183 |
| بطارية كيوصن للكراسي المتحركة 33 امبير AGM BATTERY 12V 33A | 12V / 33Ah | 191 |
| بطاريه NPP جل 12 فولت 26 امبير فيتنامي | 12V / 26Ah | 200 |
Common mistakes to avoid
- Comparing amp-hours only and ignoring voltage, ending up with four times less energy than needed
- Discharging lead acid below 50%, which cuts life to less than half
- Picking a bank that does not match the inverter voltage, so charging fails or runs inefficiently
- Thin cable or a long run between bank and inverter, causing voltage drop and lost power
- Mixing new and old packs, or different capacities, on the same bus
Next step
Send your load list and required hours over WhatsApp, or use the on-site system calculator to size the battery bank and array.
Technical advice is free, and the recommendation is based on your real consumption, inverter voltage and installation location rather than on the largest battery in stock.
Frequently asked questions
Should I use the AC's nameplate rating?
Use its real consumption; inverter ACs draw well under peak most of the time, but keep headroom for startup current.
Can I expand the bank later?
Yes with parallel-capable lithium modules of the same model and age; mixing new with old units drags the bank down.
Related pages
- Solar Battery Price Guide for Saudi Arabia
- Solar Battery Maintenance
- Off-Grid vs Hybrid Storage Systems
- Safety Standards for Energy Storage Batteries
- Lithium Solar Batteries
- LiFePO4 Solar Batteries
- Gel Solar Batteries
- Solar Energy Storage Batteries
- 48V Solar Batteries
- Choosing a Battery That Matches Your Inverter
Internal page ID: EN-GUIDE-000005